ORVALDI Liebert NX serie - 3 phase 20-200kVA

 ORVALDI Liebert NX available as 12 popular powers: 10, 15, 20, 30, 40, 60, 80, 100, 120, 140, 160, 200kVA (400V, 50/60Hz). 10-40kVA cabinet include battery for basic runtime. Bigger units has separate battery cabinets or open racks.

NEW!!!  ORVALDI Liebert NX 10, 15 i 20kVA  also in topology 3/1 phase !!!


Application :  Application: Data Centers, Inteligent Building, Telcom Centers, industry
 
Today’s advanced digital computing, communications, process control and medical systems require power protection  that is just as innovative. These systems, however, face many of the traditional threats to their availability - foremost among them is a lack of high quality power required to operate sensitive electronics.
Orvaldi’s goal is solving these challenges with a power solution that combines high performance, compact size, reliability and cost-efficiency.
Orvaldi NX is the Next Generation of True On-Line, Double-Conversion digital UPS. Designed to meet the high availability power needs of a wide variety of applications, the series NX combines innovation, simplicity and low cost of ownership. The result is a power system that delivers both reliability and a return on investment beyond what has been traditionally offered.
 
The system’s advanced True On-Line, double conversion topology features a digital signal processor (DSP) controlled IGBT rectifier and a digital signal processor (DSP) controlled IGBT inverter.
DSP Power Factor Corrected IGBT Rectifier
The rectifier provides ˇÝ 0.99 Input Power Factor (PF), less than 3% of Input Current Total Harmonic Distortion (THDi) and the widest input voltage window and frequency tolerances.
Near to Unity Power Factor ensures maximization of active power leading to reduced electricity pay-out, minimization of cables, associated switchgear and backup generator sizing requirements leading to reduced investment costs. Low input current THDi avoids disturbance to other loads connected upstream the power distribution bus without the need
to oversize generator set.
Wide input voltage window and frequency tolerances contribute to higher battery life by minimizing battery usage. High performance rectifier design helps low Neutral potential over ground and thus ensures safety of equipment.
DSP Controlled IGBT inverter
Advanced inverter control technology provides the highest output power quality, ensuring very clean output voltage waveform (very low THDv) to protect connected loads. It operates under a wide variety of conditions, handling 100% non-linear loads with 3:1 crest factor, as well as 100% unbalanced loading.
The inverter control makes Orvaldi NX to be suitable for the widest ranges of loads required by the market; including 0.9 leading PF loads.
 
Technical data

 
Models NXe NXa
 
Rated Power @ 0.8 PF [kVA]
10 15 20 30 40 60 80 100 120 140* 160* 200*
Rectifier Input
 
Rectifier Type
 IGBT-based Vector Controlled PFC (PF Corrected)
Input Voltage [Vac]
380 / 400 / 415 (Accepted from 305 to 477 without batt. Use)
Input Frequency [Hz]
50 or 60 (Accepted range from 40 to 70)
Input Current THD
<3% (without any Filter)
Input Power Factor .
 0.99 (without any Filter)
Power Walk-In [s]
5 to 30 (selectable)
Bypass Input
 
Input Voltage [Vac]
380 / 400 / 415
Battery
 
Battery Type
 VRLA (Valve Regulated Lead Acid) or Wet / Flooded or NiCd
End-Cell Voltage [Vdc/Cell]
Selectable from 1.60 to 1.90 (for VRLA)
DC Ripple Current (float)
 <5% (of C10 AH capacity) RMS value
DC Ripple Voltage (float & const V Ch)
 <1% (RMS value)
Temp. Comp. Charge
Standard (where internal batteries 10, 15, 20, 30, 40 kVA) and Optional (for all other battery configurations)
Output
 
Inverter Type
 IGBT-based Vector, Repetitive & PI Controlled
Output Power [kW]
8 12 16 24 32 48 64 80 96 112 128 160
Output Voltage [Vac]
380 / 400 / 415 +/- 0.5 Regulation (3-phase RMS average)
Output Frequency [Hz]
 50 or 60 with +/- 0.05 Regulation
Output Voltage THD
 1% (max)
Max. Load Crest Factor
 3:1 (compliant with IEC 62040-3)
Transient Volt. Resp. [ms]
10 to recover ± 5% of Nominal Voltage for 0% to 100% or 100% to 0% step load
Max. Leading PF Load
Up to 0.9
Voltage Displacement [°el]
120°+/-10 el (with 100% unbalanced load)
Overload
110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute
Efficiency
 
AC-AC
up to 96%
Physical Parameters
 
Width [mm]
600 600 700 1000
Depth [mm]
 700 825 825 825
Height [mm]
1400 1600 1800 1800
Weight (approx.)
 
without batt. [kg]
180 204 204 312 341 401 445 720 720 824 973 973
UPS Enclosure IP
 IP 20 (even with open front door)
Standards
IEC 62040-3, IEC 62040-2, IEC 62040-1-1, IEC 60146-1-1, IEC 61000-4-2, 4, 5, 6, 8,11, EN 50091-1-1, EN 50091-2, EN 50091-3, EN 60950, EN 60529, ANSI C62.41 (IEEE 587)
EMC Class
Class-A (Applicable for both Radiated & Conducted)
Environmental
 
Storage Temp. [°C]
 -20 to 70 (UPS) & -20 to 30 (Battery)
Operating Temp. [°C]
 0 to 40 (UPS) & 25 +/-5 (Battery)
Relative Humidity
 0 to 95% (non-condensing)
Maximum Altitude [m]
 1000 (as per IEC 62040/3)